Overfill Prevention & Grounding System – Top Loading
Description
Overfill Prevention and Grounding Systems provide overfill protection as well as grounding verification and are designed for top and bottom loading of tank trucks, rail cars, etc.
Overfill prevention and ground verification controller has the function of static conducting and overfill prevention. Static ground monitoring system is used in the loading system of liquid chemical products. Tank truck static grounding protection can be interlocked with automatic control system. When the liquid level reaches the sensor or there is ineffective grounding, Explosion-proof electrostatic grounding alarm will send out acousto-optic alarm and output signal to stop the valve and pump to prevent overfill and ensure static grounding.
Material
Body: Aluminum alloy
Conductor Material: Copper
Technical Data
Item |
RE1502 |
Input Power |
85VACto 250VAC @ 47 to 440Hz |
Input current |
<35mA |
Respond Time |
<2 Seconds |
Output Signal |
30V DC@10A /250V AC@10A |
Ingress Protection |
IP65 |
Spiral Cable |
Extendable to 6m (20ft) |
Alarm volume (Alarm Volume) |
>90dB |
Explosion proof class |
ExdiaIIBT4 G |
Working temperature |
-40-60ºC |
Packing size |
40X35X40 cm |
Net weight |
15.0kgs |
Gross weight |
16.7kgs |
Packing |
1pc/Carton |
Feature
1) Output signal and interlock with computer system.
2) The sensor has self-checking function. It gives malfunction alarm when it is at fault.
3) Provide on-site acousto-optic alarm, clear and visible.
4) LED display indicates the resistance value of the ground connection
5) Upon the loss of a ground connection or an overfill condition, the system will send a signal to immediately shut off the loading operation
6) Continuous self-check and alert feature to insure the system is working properly